- 600 Volts
-
Copper Conductor
-
Thermoplastic Insulation / Nylon Sheath
-
Heat, Moisture, Gasoline, and Oil Resistant
-
Sizes AWG and Larger Rated THWN-2
-
All Stranded Sizes Rated MTW and THWN
-
Sizes 14 Through 6 AWG Rated AWM (105°C)
-
Sizes 14 Through 1 AWG Rated VW-1
-
Size 1/0 AWG and Larger Listed for CT Use
-
Black Size 2 AWG and Larger Listed Sunlight-Resistant
APPLICATIONS
- Pro-Line Type THHN or THWN-2 conductors are primarily used in conduit and cable trays for services, feeders, and branch circuits in commercial or industrial applications as specified in the National Electrical Code.
- When used as Type THHN, conductor is suitable for use in dry locations at temperatures not to exceed 90°C.
- When used as Type THWN-2, conductor is suitable for use in wet or dry locations at temperatures not to exceed 90°C or not to exceed 75°C when exposed to oil or coolant.
- When used as Type MTW, conductor is suitable for use in wet locations or when exposed to oil or coolant at temperatures not to exceed 60°C or dry locations at temperatures not to exceed 90°C (with ampacity limited to that for 75°C conductor temperature per NFPA 79).
- Conductor temperatures not to exceed 105°C in dry locations when rated AWM and used as appliance wiring material. Voltage for all applications is 600 volts.
STANDARDS AND REFERENCES
Pro-Line Type THHN or THWN-2 or MTW (also AWM) meets or exceeds all applicable ASTM specifications, UL Standard 83, UL Standard 1063 (MTW), Federal Specification A-A-59544, and requirements of the National Electrical Code.
CONSTRUCTION
- Pro-Line Type THHN or THWN-2 or MTW copper conductors are annealed (soft) copper, insulated with a tough heat and moisture resistant polyvinyl chloride (PVC), over which a nylon (polyamide) or UL-listed equal jacket is applied.
- Available in black, white, red, blue, green, yellow, brown, orange, and gray; some colors standard, some subject to economic order quantity.
- Conductor sizes 2 AWG and larger listed and marked sunlight-resistant in black only.
WEIGHTS, MEASUREMENTS AND PACKAGING
RECOMMENDED SPECIFICATIONS
MTW or THHN or THWN-2
Conductors shall be UL-listed Type MTW or THHN or THWN-2 gasoline and oil resistant II, suitable for operations at 600 volts as specified in the National Electrical Code. Sizes 14 through 1 AWG shall be rated VW-1, larger sizes shall be listed for CT use. Sizes 2 AWG and larger listed and marked sunlight-resistant in black only. Conductors shall be annealed copper, insulated with high-heat and moisture resistant PVC, jacketed with abrasion, moisture, gasoline, and oil resistant nylon or listed equivalent. THHN shall be PRO-LINE WIRE & CABLE or approved equal.
AWM
Conductors shall be UL-listed Type THHN or THWN-2 or MTW or AWM, suitable for operation at 600 volts at conductor temperatures not to exceed 105°C.