XHHW-2

StumbleUponEmail
Category:

Description

 

  • 600 Volts
  • Copper Conductor
  • Cross-Linked Polyethylene Insulation (XLP)
  • High-Heat and Moisture Resistant
  • Sizes 14 Through 8 AWG Also Rated SIS
  • Black Sizes 2 AWG and Larger Sunlight-Resistant

 

APPLICATIONS

  • Pro-Line Type XHHW-2 conductors are primarily used in conduit or other recognized raceways for services, feeders, and branch circuit wiring, as specified in the National Electrical Code.
  • XHHW-2 conductors may be used in wet or dry locations at temperatures not to exceed 90°C
  • Voltage rating for XHHW-2 conductors is 600 volts

STANDARDS AND REFERENCES

Pro-Line Type XHHW-2 conductors meet or exceed UL Standard 44, Federal Specification A-A-59544, and requirements of the National Electrical Code. Type XHHW-2 meets and exceeds all construction requirements of ICEA S-95-658 (NEMA WC 70) – Nonshielded 0 – 2 kV Cables, with testing frequencies based on UL requirements.

CONSTRUCTION

  • Pro-Line Type XHHW-2 copper conductors are annealed (soft) copper. Insulation is an abrasion, moisture, and heat resistant cross-linked polyethylene (XLP)
  • Sizes 14, 12, and 10 AWG available in black, white, red, blue, yellow, green, orange, brown, purple, and gray
  • Conductor sizes 2 AWG and larger listed and marked sunlight resistant in black only
ALTERNATE CONSTRUCTION
  • Pro-Line Type XHHW-2 copper conductors are also available in sizes 1/0 AWG and larger rated for cable tray use and sunlight resistant
  • Specify XHHW-2 for CT use when requesting quote or ordering

WEIGHTS, MEASUREMENTS AND PACKAGING

RECOMMENDED SPECIFICATIONS
RECOMMENDED SAMPLE SPECIFICATIONS

Conductors shall be UL-listed Type XHHW-2, suitable for operation at 600 volts or less in wet or dry locations, at temperatures not to exceed 90°C. Conductors shall be annealed copper. XHHW-2 shall be PRO-LINE WIRE & CABLE or approved equal.

CABLE TRAY RELATED RECOMMENDED SAMPLE SPECIFICATIONS
Conductor shall be UL-listed Type XHHW-2 rated for cable tray use and sunlight resistance. Also, suitable for operation at 600 volts or less in wet or dry locations, at temperatures not to exceed 90°C. Conductors shall be annealed copper. XHHW-2 shall be PRO-LINE WIRE & CABLE or approved equal.

 

45