Description
- 600 Volts
-
Copper Conductor
-
Sunlight, Moisture, and Fungus Resistant
-
Overall Thermoplastic Insulation (PVC)
APPLICATIONS
- Pro-Line Type UF-B cable is generally used as feeder to outside post lamps, pumps, and other loads or apparatus fed from a distribution point in an existing building as specified in the National Electrical Code
- UF-B cable may be used underground, including direct burial
- Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code
- UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 volts
STANDARDS AND REFERENCES
Pro-Line Type UF-B cable meets or exceeds UL Standard 83, UL Standard 493, Federal Specification A-A-59544, and requirements of the National Electrical Code.
CONSTRUCTION
- Pro-Line Type UF-B cable is manufactured as a 2 or 3 conductor cable, with or without a ground wire
- Copper conductors are annealed (soft) copper, solid or compressed stranded
- Phase conductors are polyvinyl chloride (PVC) insulated, nylon jacketed, color coded for identification purposes
- Jacketed with sunlight, moisture and fungus resistant gray PVC